Deye · Three-phase String Inverter

Deye SUN 18/20/25K G05

Three-phase string inverter family with 18kW, 20kW and 25kW models, 2 MPP trackers, up to 98.6% maximum efficiency and IP65 protection.

  • 18-25kW
  • 2 MPPTs
  • Up to 98.6% max. efficiency
  • IP65
Deye SUN-18/20/25K-G05 three-phase string PV inverter
SUN-18K-G05 / SUN-20K-G05 / SUN-25K-G05

Available Models

Three listed TRESUN output options

TRESUN navigation lists 18/20/25K-G05. Values below are taken from the Deye SUN-18-25K-G05 datasheet.

Model Nominal AC power Recommended PV power MPPTs Max. efficiency Weight
SUN-18K-G0518,000W23,400W298.5%20kg
SUN-20K-G0520,000W26,000W298.6%20kg
SUN-25K-G0525,000W32,500W298.6%20kg

Datasheet Features

Features

01

2 MPPT architecture

Two MPP trackers covering typical commercial rooftop string layouts.

02

Up to 98.6% efficiency

Maximum efficiency is up to 98.6% and MPPT efficiency is above 99%.

03

Zero export and VSG

Zero-export application and VSG application are listed for grid-connection projects.

04

Specified protection

Type II SPD is specified on DC and AC sides. String monitoring and anti-PID are optional. Protection degree is IP65.

Product Family

Specifications

Deye SUN-18/20/25K-G05 three-phase string PV inverter front view

For preliminary product matching. Confirm the exact model and destination-market grid requirements before quotation.

Maximum DC voltage
1100V class / 1000V family rating by datasheet revision
Start voltage
250V
MPPT voltage range
200-850V
Nominal AC voltage
220V / 380V, 230V / 400V
AC grid connection
3L / N / PE
THDi
<3%
Protection degree
IP65
Cooling
Intelligent air cooling
Operating temperature
-25 C to +60 C, derating above 45 C
Dimensions (W / H / D)
362 / 527 / 220mm
Weight
20kg
Interfaces
RS485 / RS232 / WiFi / LAN

Application Fit

Three-phase commercial rooftop PV projects

The SUN-18/20/25K-G05 family is intended for three-phase commercial rooftops requiring 18-25kW nominal AC output.

Technical Source

Manufacturer datasheet

Deye SUN-18-25K-G05 datasheet. Specifications may change; confirm the exact model before order placement.

View Official Datasheet

Project Enquiry

Request model matching and a quotation

Please provide the target model or output power, grid voltage, PV string design, destination market and required quantity.